MindSparc
HomeProductsOpen SourceAbout
AmpRule

NEC guides

Worked explanations of the calculations that come up on the job, each one citing the article it comes from. Written to be useful on their own — you do not need the app to get the answer.

  • What actually changed in the NEC 2026

    A working electrician's list of the NEC 2026 changes that move numbers on the job: Table 310.16 gained rows, 250.122 letters shifted, and one renumbered article now points somewhere else entirely.

    Read
  • How to calculate box fill, item by item

    Box fill is six separate counts added together, not one. The volume table, what counts as a conductor, why device yokes are doubled, and the three different meanings of 'largest conductor' that make this easy to get wrong.

    Read
  • Where the 40% conduit fill rule comes from, and when it is not 40%

    The 40% fill limit only applies to more than two conductors. One conductor gets 53%, two conductors get 31%, and a short nipple gets 60%. Plus the jam ratio, which the percentages will not warn you about.

    Read

AmpRule is not affiliated with or endorsed by NFPA. NEC and National Electrical Code are trademarks of the National Fire Protection Association. Always verify against the edition adopted by your AHJ.

MindSparc

Pioneering the future of artificial intelligence. Delivering distributed global solutions.

Global HQ

Navigate

  • About Us
  • Products
  • Open Source
  • Contact

Connect

  • GitHub
  • admin@mindsparc.ai

© 2026 MindSparc AI Pte. Ltd. All rights reserved.